EMA-010: Project information must not have duplicate parameters

BIM

IC2665
BIM

Note: This EMA describes a Revit-specific solution.

When publishing a new building under an existing location, a message appears stating that the location with a specific GlobalUid does not exist on the server. The cause here is that duplicate parameters are stored in the model under Project Information in Revit and, consequently, are not present in the IFC file.

Data transfer dialog showing error: Location 'LEV' with GlobalUid not found on server. Transfer aborted.
Data transfer dialog showing error: Location 'LEV' with GlobalUid not found on server. Transfer aborted.

Figure 1: Error message during data transfer

Here, it is necessary to check in Revit whether the parameters

  • IfcBuilding GUID

  • IfcProject GUID

  • IfcSite GUID

are duplicated; if so, these parameters and their duplicates must be removed and republished.

Dialog
Dialog "Projektparameter" showing list of 22 available parameters, with "IfcBuilding GUID", "IfcProject GUID", and "IfcSite GUID" highlighted. Options to add, edit, or remove parameters.

Figure 2: Screenshot from Revit